XARTU/5™ Manual Copyright© 2013
Eagle Research Corporation
®
REV 11.1.11 Page | 35
9. Press or to increase or decrease the output until the meter reads 20mA, or the
current span reference matches the field equipment. Press ent to collect the new
point.
10. Steps 5 - 9 are required only once. They may be repeated as often as necessary
while in calibration, but only the most recent point will be saved on completion of
calibration.
11. To permanently store the results of the calibration press ent, and the unit will
prompt Enter to accept Calibration. Simply press ent again to save the
calibration. Press esc to abort the calibration.
MAINTENANCE
As with any device based on solid-state electronics, actual maintenance of the RTU
should be minimal. However, there are certain guidelines that, if followed, will minimize
device failure and increase the product's service life.
ENCLOSURE MAINTENANCE
Enclosure maintenance is a program of routine inspections to ensure the integrity of the
lid's seal and the various ports in the enclosure's exterior. Excessive moisture can ruin
an RTU if allowed to accumulate within the enclosure. Although the circuit boards
themselves are conformally coated to protect against humidity, the wiring
interconnections and various exposed metal surfaces are susceptible to corrosion in
extreme cases of interior humidity. Here are some checks you should periodically make
of the enclosure:
1. Ensure that the mounting arrangement for the unit is secure and provides a stable
platform for termination of the pressure tubing.
2. Verify the integrity of the enclosure lid seal. Check the lid gasket for deterioration,
chemical damage, tears, or compression.
3. Check for damaged cord grips and a missing or damaged RS-232C port cap.
4. Verify the integrity of the enclosure lid seal. Check the lid gasket for deterioration,
chemical
damage, tears, or compression.
5. Check for damaged cord grips and a missing or damaged RS-232C port cap.
6. Examine the RS-232C port itself. Ensure that the port's mounting screws are secure
and
provide firm support when attaching a serial cable.