CN-6000
Series
C-8
Parameter
Functions Graph Applications
LIN
Outputs
asinput
value
Display
Input
Y=AX+B
Standard
characteristics.
Inputfor
linearity.
ROOT
Outputs
the
rooted
(
)input
value
Display
Input
Y=0(X<0)
Y=A(X)+B
(X≥0)
Usedfor
measuringows
bypressure
signal.
SQAR
Outputs
the
squared
input
value
Display
Input
Y=A(X)
2
+B
(X>0)
Y=-A(X)
2
+B
(X<0)
Usedfor
outputting
differential
pressurebyow
signal.
TUF
Referto‘Twounitfunction’
Thisfunctionistosetoutputscaleandrangefordisplay
valuefortransmissionoutput.
Whentheinputvaluesetat
lOU1
/
lOU2
isdisplayed,
theoutputvaluesetat
lOR1
/
lOR2
istransmitted.
Whentheinputvaluesetat
hOU1
/
hOU2
isdisplayed,
theoutputvaluesetat
hOR1
/
hOR2
istransmitted.
■ Transmission output range
[Program mode: lOR , hOR ]
Transmission output scale
[Program mode: lOU , hOU ]
Relationamonginputrange,userinputrange,display
scale,transmissionscale,andoutputrange
Thebelowgureistheexamplefor4to20mAinputand
0-20mAtransmissionoutput.
Whendisplayvalueis100,itoutputs4mA.
Whendisplayvalueis900,itoutputs20mA.
Whenconnectingapressuresensor,compound
pressurewhichisbelowatmosphericpressure(0)isfor
vacuumasmmHgandwhichisatmosphericpressure
oroveritisforpositivepressureaskg/cm
2
.
Atmosphericpressureis0kg/cm
2
.Whenthisunit
doesnotdisplay0kg/cm
2
,youcancorrectzero-point
adjustmentfunction.
Whenusingtwounitfunction,
L-SC
isxedas
-760
.
L-SC
parameterisdisplayedbutyoucannotsetthis.
Youcanset
H-SC
within
0
to
9999
range.
Thisfunctionistosetanaloginputvalueforatmospheric
pressure(0)atanaloginputrange.
Input special function [Program mode: InSF]
٧
Two Unit Function [
TUF
]
■ Atmospheric pressure (0) setting
for Two Unit Function
[Program mode: )PSI, InSF: TUF]
Whenselectinganaloginput,thisfunctionistodisplaythe
calculatedactualvaluebysquare,root(),ortwounit
function(TUF)asdisplayvalue.
DisplayvalueandmAoutputvaluefor
SQAR
:
DisplayvalueandmAoutputvaluefor
ROOT
:
■ Input and transmission output extension
[Program mode : ExIO]
Thisfunctionistoextendanaloginputand4to20mA,
0-10VDCtransmissionoutputto5%or10%range.
Thebelowtableisthecaseof4to20mAtransmission
outputrangesetting.
Thisparameterisnotdisplayedfornottransmission
output(4-20mA,0-10V)model,orforselecting
temperaturesensorinput.
Below0mA,0VDCcannotextend.
±1VDC,10VDCinputareavailabletoextendonly5%.
Mode Operation
0P
Outputs4to20mAwithinanaloginput
range.
5P
Outputs3.2to20.8mAfor5%outofthe
analoginputrange.
10P
Outputs2.4to21.6mAfor10%outofthe
analoginputrange.
ThisfunctionistoselectOUT1orOUT2forBardisplayof
transmissionoutputscale.
Onlyforthemodelwhichhastwotransmissionoutputs
(CN-6
-C2/V2),thisparameterisdisplayed.
■ Bar display channel
[Program mode: BAR, User level: HIGH]
Ex)Whenpressurerangeis 760.0mmHgto3.000kg/
cm
2
,andpressuretransmitteroutputs4-20mAand
itoutputs8.00mAforatmosphericpressure(0),set
inputspecialfunctionas
TUF
,
H-SC
:
3000
,
dP
:
)000
,
)PSI
:
0800
.Thisunitdisplaysfor4mAinput
as
-760
,for8mAinputas
)000
and20mAinput
as
#000
.
8mA
ThisfunctionisonlyforCN-610
.
Displayvalue={()×(
H-SC
-
L-SC
)}+
L-SC
(outputvalue)
Inputvalue-
L-RG
H-RG
-
L-RG
2
Displayvalue={()×(
H-SC
-
L-SC
)}+
L-SC
(outputvalue)
Inputvalue-L-RG
H-RG
-
L-RG
Display
Input
Display
Output
Display
Output
Inputrange
User
inputrange
(6mAto16mA)
Displayscale
(0to1000)
Outputscale
4mA
transmission
20mA
transmission
Outputrange