CN-6000
Series
C-6
■ Alarm [ AL-1, AL-2, AL-3, AL-4]
Thisproducthas1alarmor2or4alarmstooperateindividuallywhenthevalueistoohighorlow.Alarmfunctionissetbythe
combinationofalarmoperationandalarmoption.
Toclearalarm,usedigitalinputfunction(settingas
AlRE
for
DI-K
)orturnthepowerOFFandON.
※
Forthemodelwithoutalarmoutput(CN-6
-C1/C2/V1/V2),theseparametersarenotdisplayed.
AT!A
Alarmoption
Alarmoperation
٧
Alarm operation
٧
Alarm option
Mode Name Alarmoperation Description
AT)_
ㅡ ㅡ
Noalarmoperation
AT!
Highlimitalarm
Highlimtalarm
value:800
℃
OFF
ON
PV
H
PV≥alarmtemperature,alarmisON
AT@
Lowlimitalarm
Lowlimtalarm
value:200
℃
OFF
ON
PV
H
PV≤alarmtemperature,alarmisON
SBa_
Sensorbreakalarm
ㅡ
ItwillbeONwhenitdetectssensordisconnection.
Sensorbreakalarmdoesnothavealarmoption.
Mode Name Descriptions
AT .A
Standardalarm Ifitisanalarmcondition,alarmoutputisON.Unlessanalarmcondition,alarmoutputisOFF.
AT .B
Alarmlatch
Ifitisanalarmcondition,alarmoutputisON.Beforeclearingthealarm,anONconditionis
latched.(Holdingthealarmoutput)
AT .C
Standbysequence
Firstalarmconditionisignored.Fromthesecondalarmcondition,standardalarmoperates.
WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,
standardalarmoperates.
AT .D
Alarmlatchand
standbysequence
Ifitisanalarmcondition,itoperatesbothalarmlatchandstandbysequence.
WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,
alarmlatchoperates.
※
1.OnlyforCN-610
.
※
H:Alarmoutputhysteresis
※
1
■ Alarm output hysteresis
[Program mode : A-HY]
SettheintervalofON/OFFalarmoutput.
ThesethysteresisisappliedtoAL1toAL4anditisas
below.
※
Ex)
A-HY
4,highlimitalarmvalue:800,
lowlimitalarmvalue:200
Highlimit
alarmvalue
800
800
ON
796
OFF
A-HY
:4
Lowlimit
alarmvalue
200
200
ON
204
OFF
A-HY
:4
■ High/Low peak monitoring
[Monitoring mode: hPEK, lPEK]
Thisfunctionistosavehigh/lowpeaktochecktheinvisible
abnormalconditionofsystemat[
hPEK
]or[
lPEK
]in
monitoringmode.
Whenthehigh/lowpeakisoutofthetemperaturerange,
itdisplays
HHHH
or
LLLL
.
Toinitializehigh/lowpeak,pressthe4,3keysatthe
sametimefor3sec.at[
hPEK
]or[
lPEK
].
Inthiscase,peakvalueisthepresentinputvalue.
■ Error
Display Descriptions Troubleshooting
LLLL
Flasheswhenmeasured
sensorinputislowerthanthe
temperaturerange.
Wheninputis
movedwithinthe
temperaturerange,
itiscleared.
HHHH
Flasheswhenmeasuredsen-
sorinputishigherthanthe
temperaturerange
BURN
Flasheswhenthesensoris
breakornotconnected.
Checktemperature
sensorconnection.
ERR
Flasheswhenthereiserrorto
SV.
Checksetconditions
andre-setit.
ERR2
Flasheswhen[
IN-P
]setting
andinputtypeselectionswitch
settingarenotsame.
Checkinputtype.
※
1
※
1.OnlyforCN-610
.
Functions
Kommentare zu diesen Handbüchern